Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P20 — 20 kVA prime / 22 kVA standby Perkins diesel generator

20 kVA prime / 22 kVA standby, powered by a Perkins 404A(D)-22G1 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 20 kVA prime
  • 22 kVA standby
  • Perkins 404A(D)-22G1
  • 1-year warranty
4U-P20 — 20 kVA prime / 22 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P20
Standby (ESP)22 kVA / 17.6 kW
Prime (PRP)20 kVA / 16 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P20
Make / modelPerkins 404A(D)-22G1
Cylinders4 in-line
Displacement2.22 L
Bore × stroke84 × 100 mm
AspirationNaturally aspirated
GoverningMechanical
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity7 L
Lube oil capacity10.6 L

Alternator

Alternator — 4U-P20
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A40-F
Stamford frameS0L2G1
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P20
50 % prime load2.9 L/h
75 % prime load4 L/h
100 % prime load5.3 L/h
Standby rating6.1 L/h

Dimensions & weight

Dimensions & weight — 4U-P20
Open set (L × W × H)1540 × 750 × 1245 mm
Open set weight555 kg
Silent canopy (L × W × H)2152 × 1004 × 1342 mm
Canopy weight855 kg
Base fuel tank169 L
Noise @ 7 m68 dB(A) ± 3

Control & protection

Control & protection — 4U-P20
ControllerDeep Sea DSE4520 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P131413Perkins 403A(D)-15G13.7Datasheet
4U-P1516.515Perkins 403A-15G23.7Datasheet
4U-P202220Perkins 404A(D)-22G15.3Datasheet
4U-P242724Perkins 404D-22G—Datasheet
4U-P303330Perkins 1103A-33G7.2Datasheet
All 42 Perkins models →
CallWhatsApp