Perkins generating set · 50 Hz
4U-P15 — 15 kVA prime / 16.5 kVA standby Perkins diesel generator
15 kVA prime / 16.5 kVA standby, powered by a Perkins 403A-15G2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.
- 15 kVA prime
- 16.5 kVA standby
- Perkins 403A-15G2
- 1-year warranty

Output ratings
| Standby (ESP) | 16.5 kVA / 13.2 kW |
|---|---|
| Prime (PRP) | 15 kVA / 12 kW |
| Voltage / frequency | 400/230 V · 3-phase · 50 Hz · 1500 rpm |
| Power factor | 0.8 |
| Other voltages | 380/220 · 415/240 · 440/254 · 480/277 V |
Engine
| Make / model | Perkins 403A-15G2 |
|---|---|
| Cylinders | 3 in-line |
| Displacement | 1.5 L |
| Bore × stroke | 84 × 90 mm |
| Aspiration | Naturally aspirated |
| Governing | Mechanical |
| Cooling | Water cooled, radiator for 50 °C ambient |
| Coolant capacity | 6 L |
| Lube oil capacity | 6 L |
Alternator
| Make | 4U · Leroy-Somer | Stamford |
|---|---|
| Leroy-Somer frame | TAL-A40-D |
| Stamford frame | S0L1P1 |
| Type | Self-excited, 4-pole, single bearing |
| Insulation / protection | Class H · IP23 |
| Voltage regulation | ± 1 % |
Fuel consumption
| 50 % prime load | 2 L/h |
|---|---|
| 75 % prime load | 2.8 L/h |
| 100 % prime load | 3.7 L/h |
| Standby rating | 4.1 L/h |
Dimensions & weight
| Open set (L × W × H) | 1635 × 750 × 1260 mm |
|---|---|
| Open set weight | 495 kg |
| Silent canopy (L × W × H) | 2152 × 1004 × 1342 mm |
| Canopy weight | 765 kg |
| Base fuel tank | 169 L |
| Noise @ 7 m | 68 dB(A) ± 3 |
Control & protection
| Controller | Deep Sea DSE4520 MKII — auto start / AMF |
|---|---|
| Main breaker | 3-pole LS MCCB |
| Shutdowns & alarms | Over/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop |
| Warranty | 12 months or 1,000 running hours, whichever first |
- Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
- Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
- Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.