Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P1710 — 1,710 kVA prime / 1,875 kVA standby Perkins diesel generator

1710 kVA prime / 1875 kVA standby, powered by a Perkins 4012-46TAG3A engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 1710 kVA prime
  • 1875 kVA standby
  • Perkins 4012-46TAG3A
  • 1-year warranty
4U-P1710 — 1,710 kVA prime / 1,875 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P1710
Standby (ESP)1,875 kVA / 1,500 kW
Prime (PRP)1,710 kVA / 1,368 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P1710
Make / modelPerkins 4012-46TAG3A
Cylinders12 in 60° V
Displacement45.8 L
Bore × stroke160 × 190 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity210 L
Lube oil capacity177 L

Alternator

Alternator — 4U-P1710
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameLSA 51.2 S5
Stamford frameS7L1D-E41
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P1710
Fuel consumptionOn request

Dimensions & weight

Dimensions & weight — 4U-P1710
Open set (L × W × H)5170 × 2275 × 2875 mm
Open set weight11,500 kg
Silent canopy (L × W × H)9000 × 2350 × 3850 mm
Canopy weight18,500 kg
Base fuel tankExternal day tank (sized to site)
Noise @ 7 m87 dB(A) ± 3

Control & protection

Control & protection — 4U-P1710
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P12501,3751,250Perkins 4012-46TWG2A266Datasheet
4U-P15001,6501,500Perkins 4012-46TAG2A310Datasheet
4U-P17101,8751,710Perkins 4012-46TAG3A—Datasheet
4U-P18502,0001,850Perkins 4016-61TRG1383Datasheet
4U-P20002,2502,000Perkins 4016-61TRG2434Datasheet
All 42 Perkins models →