Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P1500 — 1,500 kVA prime / 1,650 kVA standby Perkins diesel generator

1500 kVA prime / 1650 kVA standby, powered by a Perkins 4012-46TAG2A engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy or container, with delivery, installation and commissioning across the UAE.

  • 1500 kVA prime
  • 1650 kVA standby
  • Perkins 4012-46TAG2A
  • 1-year warranty
4U-P1500 — 1,500 kVA prime / 1,650 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P1500
Standby (ESP)1,650 kVA / 1,320 kW
Prime (PRP)1,500 kVA / 1,200 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P1500
Make / modelPerkins 4012-46TAG2A
Cylinders12 in 60° V
Displacement45.8 L
Bore × stroke160 × 190 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity177 L
Lube oil capacity177 L

Alternator

Alternator — 4U-P1500
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameLSA 50.2 L8
Stamford frameS7L1D-D41
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P1500
50 % prime load234 L/h
75 % prime load249 L/h
100 % prime load310 L/h
Standby rating341 L/h

Dimensions & weight

Dimensions & weight — 4U-P1500
Open set (L × W × H)5100 × 2275 × 2605 mm
Open set weight11,100 kg
Container40 ft ISO HC container
Containerised weight15,400 kg
Base fuel tankExternal day tank (sized to site)
Noise @ 7 m87 dB(A) ± 3

Control & protection

Control & protection — 4U-P1500
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P10001,1001,000Perkins 4008-TAG2—Datasheet
4U-P12501,3751,250Perkins 4012-46TWG2A266Datasheet
4U-P15001,6501,500Perkins 4012-46TAG2A310Datasheet
4U-P17101,8751,710Perkins 4012-46TAG3A—Datasheet
4U-P18502,0001,850Perkins 4016-61TRG1383Datasheet
All 42 Perkins models →
CallWhatsApp