Cummins generating set · 50 Hz

4U-C200 — 200 kVA prime / 220 kVA standby Cummins diesel generator

200 kVA prime / 220 kVA standby, powered by a Cummins 6CTAA8.3-G2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 200 kVA prime
  • 220 kVA standby
  • Cummins 6CTAA8.3-G2
  • 1-year warranty
4U-C200 — 200 kVA prime / 220 kVA standby Cummins diesel generator

Output ratings

Output ratings — 4U-C200
Standby (ESP)220 kVA / 176 kW
Prime (PRP)200 kVA / 160 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-C200
Make / modelCummins 6CTAA8.3-G2
Cylinders6 in-line
Displacement8.3 L
Bore × stroke114 × 135 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 48 °C ambient
Coolant capacity12 L
Lube oil capacity23.8 L

Alternator

Alternator — 4U-C200
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A44-M
Stamford frameUCI274H
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-C200
50 % prime load23 L/h
75 % prime load34 L/h
100 % prime load46 L/h
Standby rating51 L/h

Dimensions & weight

Dimensions & weight — 4U-C200
Open set (L × W × H)2610 × 1265 × 1715 mm
Open set weight1,685 kg
Silent canopy (L × W × H)3894 × 1355 × 2207 mm
Canopy weight2,547 kg
Base fuel tank543 L
Noise @ 7 m77 dB(A) ± 3

Control & protection

Control & protection — 4U-C200
ControllerDeep Sea DSE4520 — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-C180200180Cummins 6CTA8.3-G142Datasheet
4U-C180B200180Cummins QSB7-G442Datasheet
4U-C200220200Cummins 6CTAA8.3-G246Datasheet
4U-C200B220200Cummins QSB7-G546Datasheet
4U-C250270250Cummins 6LTAA8.9-G256Datasheet
All 44 Cummins models →