Skip to content
4U PowerGenerationFZC

Cummins generating set · 50 Hz

4U-C180B — 180 kVA prime / 200 kVA standby Cummins diesel generator

180 kVA prime / 200 kVA standby, powered by a Cummins QSB7-G4 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 180 kVA prime
  • 200 kVA standby
  • Cummins QSB7-G4
  • 1-year warranty
4U-C180B — 180 kVA prime / 200 kVA standby Cummins diesel generator

Output ratings

Output ratings — 4U-C180B
Standby (ESP)200 kVA / 160 kW
Prime (PRP)180 kVA / 144 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-C180B
Make / modelCummins QSB7-G4
Cylinders6 in-line
Displacement6.7 L
Bore × stroke107 × 124 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 60 °C ambient
Coolant capacity26 L
Lube oil capacity18.9 L

Alternator

Alternator — 4U-C180B
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A44-L
Stamford frameUCI274G
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-C180B
50 % prime load24 L/h
75 % prime load34 L/h
100 % prime load42 L/h
Standby rating48 L/h

Dimensions & weight

Dimensions & weight — 4U-C180B
Open set (L × W × H)2800 × 900 × 1650 mm
Open set weight1,800 kg
Silent canopy (L × W × H)3764 × 1155 × 1881 mm
Canopy weight2,170 kg
Base fuel tank450 L
Noise @ 7 m78 dB(A) ± 3

Control & protection

Control & protection — 4U-C180B
ControllerDeep Sea DSE4520 — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-C150B165150Cummins 6BTAA5.9-G730Datasheet
4U-C180200180Cummins 6CTA8.3-G142Datasheet
4U-C180B200180Cummins QSB7-G442Datasheet
4U-C200220200Cummins 6CTAA8.3-G246Datasheet
4U-C200B220200Cummins QSB7-G546Datasheet
All 44 Cummins models →
CallWhatsApp