Skip to content
4U PowerGenerationFZC

Cummins generating set · 50 Hz

4U-C250 — 250 kVA prime / 270 kVA standby Cummins diesel generator

250 kVA prime / 270 kVA standby, powered by a Cummins 6LTAA8.9-G2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 250 kVA prime
  • 270 kVA standby
  • Cummins 6LTAA8.9-G2
  • 1-year warranty
4U-C250 — 250 kVA prime / 270 kVA standby Cummins diesel generator

Output ratings

Output ratings — 4U-C250
Standby (ESP)270 kVA / 216 kW
Prime (PRP)250 kVA / 200 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-C250
Make / modelCummins 6LTAA8.9-G2
Cylinders6 in-line
Displacement8.9 L
Bore × stroke114 × 145 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity55.5 L
Lube oil capacity32.4 L

Alternator

Alternator — 4U-C250
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A46-D
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-C250
50 % prime load29 L/h
75 % prime load42 L/h
100 % prime load56 L/h
Standby rating64 L/h

Dimensions & weight

Dimensions & weight — 4U-C250
Open set (L × W × H)2850 × 1420 × 2130 mm
Open set weight2,650 kg
Silent canopy (L × W × H)4414 × 1614 × 2217 mm
Canopy weight3,270 kg
Base fuel tank843 L
Noise @ 7 m82 dB(A) ± 3

Control & protection

Control & protection — 4U-C250
ControllerDeep Sea DSE6120 — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-C200220200Cummins 6CTAA8.3-G246Datasheet
4U-C200B220200Cummins QSB7-G546Datasheet
4U-C250270250Cummins 6LTAA8.9-G256Datasheet
4U-C250B275250Cummins QSL9-G359Datasheet
4U-C271302271Cummins 6LTAA9.5-G356Datasheet
All 44 Cummins models →