Generator Fuel Consumption Chart: Litres per Hour from 20 to 2000 kVA

How much diesel does a generator use per hour? A consumption chart from 20 to 2000 kVA at 50%, 75% and full load, plus how to size the fuel tank.

Generator Fuel Consumption Chart: Litres per Hour from 20 to 2000 kVA

Fuel is the biggest running cost of a generator, and it decides how big the tank must be. Here is how much diesel a set uses, and how to work out your own numbers.

The quick rule

A modern diesel generator uses roughly 0.26 litres of diesel per kWh produced at 75% load. Efficiency drops at light load and is slightly worse at full load.

Litres per hour ≈ kW of load × 0.26

So a 200 kVA set (160 kW) running at 75% load (120 kW) burns about 31 litres an hour.

Consumption chart

Typical values for modern diesel sets at 0.8 power factor. Exact figures depend on engine model and site conditions — always check the datasheet for the unit quoted.

Generator (kVA) Prime kW 50% load (L/h) 75% load (L/h) 100% load (L/h)
20 16 2.2 3.1 4.3
30 24 3.4 4.7 6.5
50 40 5.6 7.8 10.8
60 48 6.7 9.4 13.0
80 64 9.0 12.5 17.3
100 80 11.2 15.6 21.6
150 120 16.8 23.4 32.4
200 160 22.4 31.2 43.2
250 200 28.0 39.0 54.0
300 240 33.6 46.8 64.8
400 320 44.8 62.4 86.4
500 400 56.0 78.0 108.0
650 520 72.8 101.4 140.4
750 600 84.0 117.0 162.0
1000 800 112.0 156.0 216.0
1250 1000 140.0 195.0 270.0
1500 1200 168.0 234.0 324.0
2000 1600 224.0 312.0 432.0

Each size has its own page with the full specs — for example the 100 kVA, 500 kVA and 1000 kVA generators.

What makes consumption go up

  • light loading — a set at 20% load burns more fuel per kWh and suffers wet stacking
  • heat — at 50 °C the radiator fan works harder and output is derated
  • dirty air filters and poor maintenance — see our maintenance checklist
  • oversizing — a set far bigger than the load wastes fuel every hour it runs

How to size the fuel tank

Tank (litres) = L/h at expected load × hours of autonomy × 1.1

The 10% covers the unusable fuel at the bottom of the tank. Example: a 500 kVA set at 75% load for 24 hours → 78 × 24 × 1.1 ≈ 2,060 litres. Standard base tanks usually give around 8 hours; longer autonomy needs a bigger base tank or an external fuel tank.

Running cost per hour

Multiply the litres per hour by the current diesel price. Over a year, 1–2 litres per hour saved by correct sizing adds up to thousands of litres — which is why getting the size right with our kVA calculator pays for itself.