Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P800 — 800 kVA prime / 900 kVA standby Perkins diesel generator

800 kVA prime / 900 kVA standby, powered by a Perkins 4006-23TAG3A engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 800 kVA prime
  • 900 kVA standby
  • Perkins 4006-23TAG3A
  • 1-year warranty
4U-P800 — 800 kVA prime / 900 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P800
Standby (ESP)900 kVA / 720 kW
Prime (PRP)800 kVA / 640 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P800
Make / modelPerkins 4006-23TAG3A
Cylinders6 in-line
Displacement22.9 L
Bore × stroke160 × 190 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity105 L
Lube oil capacity113.4 L

Alternator

Alternator — 4U-P800
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A49-C
Stamford frameS6L1D-D41
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P800
50 % prime load130 L/h
75 % prime load137 L/h
100 % prime load172 L/h
Standby rating194 L/h

Dimensions & weight

Dimensions & weight — 4U-P800
Open set (L × W × H)4320 × 2195 × 2535 mm
Open set weight6,620 kg
Silent canopy (L × W × H)5965 × 2190 × 3315 mm
Canopy weight8,765 kg
Base fuel tank1,800 L
Noise @ 7 m85 dB(A) ± 3

Control & protection

Control & protection — 4U-P800
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P746820746Perkins 4006-23TAG2A157Datasheet
4U-P770850770Perkins 2806A-E18TTAG5157Datasheet
4U-P800900800Perkins 4006-23TAG3A172Datasheet
4U-P9001,000900Perkins 4008-TAG1195Datasheet
4U-P10001,1001,000Perkins 4008-TAG2—Datasheet
All 42 Perkins models →