Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P746 — 746 kVA prime / 820 kVA standby Perkins diesel generator

746 kVA prime / 820 kVA standby, powered by a Perkins 4006-23TAG2A engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 746 kVA prime
  • 820 kVA standby
  • Perkins 4006-23TAG2A
  • 1-year warranty
4U-P746 — 746 kVA prime / 820 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P746
Standby (ESP)820 kVA / 656 kW
Prime (PRP)746 kVA / 596.8 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P746
Make / modelPerkins 4006-23TAG2A
Cylinders6 in-line
Displacement22.9 L
Bore × stroke160 × 190 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity105 L
Lube oil capacity113.4 L

Alternator

Alternator — 4U-P746
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A49-C
Stamford frameS6L1D-C41
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P746
50 % prime load121 L/h
75 % prime load127 L/h
100 % prime load157 L/h
Standby rating173 L/h

Dimensions & weight

Dimensions & weight — 4U-P746
Open set (L × W × H)4300 × 1750 × 2200 mm
Open set weight6,300 kg
Silent canopy (L × W × H)6000 × 2440 × 2590 mm
Canopy weight9,300 kg
Base fuel tank1,170 L
Noise @ 7 m86 dB(A) ± 3

Control & protection

Control & protection — 4U-P746
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P650700650Perkins 2806A-E18TAG2132Datasheet
4U-P660730660Perkins 2806A-E18TTAG4132Datasheet
4U-P746820746Perkins 4006-23TAG2A157Datasheet
4U-P770850770Perkins 2806A-E18TTAG5157Datasheet
4U-P800900800Perkins 4006-23TAG3A172Datasheet
All 42 Perkins models →