Skip to content
4U PowerGenerationFZC

Lister Petter generating set · 50 Hz

4U-L575 — 575 kVA prime / 630 kVA standby Lister Petter diesel generator

575 kVA prime / 630 kVA standby, powered by a Lister Petter LP625EG2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 575 kVA prime
  • 630 kVA standby
  • Lister Petter LP625EG2
  • 1-year warranty
4U-L575 — 575 kVA prime / 630 kVA standby Lister Petter diesel generator

Output ratings

Output ratings — 4U-L575
Standby (ESP)630 kVA / 504 kW
Prime (PRP)575 kVA / 460 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-L575
Make / modelLister Petter LP625EG2
Cylinders6 in-line
Displacement25.18 L
Bore × stroke170 × 185 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 52 °C ambient
Coolant capacity165 L
Lube oil capacity75 L

Alternator

Alternator — 4U-L575
Make4U · Leroy-Somer | Stamford
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-L575
50 % prime load68 L/h
75 % prime load94 L/h
100 % prime load124 L/h
Standby rating136 L/h

Dimensions & weight

Dimensions & weight — 4U-L575
Open set (L × W × H)3910 × 2010 × 2705 mm
Silent canopy (L × W × H)5873 × 2224 × 2817.8 mm
Base fuel tank1,835 L

Control & protection

Control & protection — 4U-L575
ControllerDeep Sea DSE6120 — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-L400440400Lister Petter LP613G287Datasheet
4U-L500545500Lister Petter LP625EG1111Datasheet
4U-L575630575Lister Petter LP625EG2124Datasheet
4U-L638695638Lister Petter LP625EG3136Datasheet
4U-L700765700Lister Petter LP625EG4148Datasheet
All 39 Lister Petter models →