Skip to content
4U PowerGenerationFZC

Lister Petter generating set · 50 Hz

4U-L350 — 350 kVA prime / 385 kVA standby Lister Petter diesel generator

350 kVA prime / 385 kVA standby, powered by a Lister Petter LP612G3 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 350 kVA prime
  • 385 kVA standby
  • Lister Petter LP612G3
  • 1-year warranty
4U-L350 — 350 kVA prime / 385 kVA standby Lister Petter diesel generator

Output ratings

Output ratings — 4U-L350
Standby (ESP)385 kVA / 308 kW
Prime (PRP)350 kVA / 280 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-L350
Make / modelLister Petter LP612G3
Cylinders6 in-line
Displacement11.8 L
Bore × stroke128 × 153 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 52 °C ambient
Coolant capacity79 L
Lube oil capacity36 L

Alternator

Alternator — 4U-L350
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A46-H
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-L350
50 % prime load37 L/h
75 % prime load54.1 L/h
100 % prime load72.9 L/h
Standby rating81 L/h

Dimensions & weight

Dimensions & weight — 4U-L350
Open set (L × W × H)3080 × 1200 × 1830 mm
Silent canopy (L × W × H)4414 × 1614 × 2235 mm
Base fuel tank760 L

Control & protection

Control & protection — 4U-L350
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-L280300280Lister Petter LP612G158.8Datasheet
4U-L325358325Lister Petter LP612G266.9Datasheet
4U-L350385350Lister Petter LP612G372.9Datasheet
4U-L375413375Lister Petter LP613G179Datasheet
4U-L400440400Lister Petter LP613G287Datasheet
All 39 Lister Petter models →