Lister Petter generating set · 50 Hz
4U-L325 — 325 kVA prime / 358 kVA standby Lister Petter diesel generator
325 kVA prime / 358 kVA standby, powered by a Lister Petter LP612G2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.
- 325 kVA prime
- 358 kVA standby
- Lister Petter LP612G2
- 1-year warranty

Output ratings
| Standby (ESP) | 358 kVA / 286 kW |
|---|---|
| Prime (PRP) | 325 kVA / 260 kW |
| Voltage / frequency | 400/230 V · 3-phase · 50 Hz · 1500 rpm |
| Power factor | 0.8 |
| Other voltages | 380/220 · 415/240 · 440/254 · 480/277 V |
Engine
| Make / model | Lister Petter LP612G2 |
|---|---|
| Cylinders | 6 in-line |
| Displacement | 11.8 L |
| Bore × stroke | 128 × 153 mm |
| Aspiration | Turbocharged, air-to-air charge cooled |
| Governing | Electronic |
| Cooling | Water cooled, radiator for 52 °C ambient |
| Coolant capacity | 79 L |
| Lube oil capacity | 36 L |
Alternator
| Make | 4U · Leroy-Somer | Stamford |
|---|---|
| Type | Self-excited, 4-pole, single bearing |
| Insulation / protection | Class H · IP23 |
| Voltage regulation | ± 1 % |
Fuel consumption
| 50 % prime load | 33.8 L/h |
|---|---|
| 75 % prime load | 49 L/h |
| 100 % prime load | 66.9 L/h |
| Standby rating | 74.3 L/h |
Dimensions & weight
| Open set (L × W × H) | 3080 × 1200 × 1830 mm |
|---|---|
| Silent canopy (L × W × H) | 4414 × 1614 × 2235 mm |
| Base fuel tank | 760 L |
Control & protection
| Controller | Deep Sea DSE6110 MKII — auto start / AMF |
|---|---|
| Main breaker | 3-pole LS MCCB |
| Shutdowns & alarms | Over/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop |
| Warranty | 12 months or 1,000 running hours, whichever first |
- Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
- Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
- Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.
Request this spec
Typical reply: within 1 working hour on WhatsApp
Nearby models
| Model | Standby kVA | Prime kVA | Engine | Fuel 100% (L/h) | Datasheet |
|---|---|---|---|---|---|
| 4U-L250 | 275 | 250 | Lister Petter LP689G3 | 55.1 | Datasheet |
| 4U-L280 | 300 | 280 | Lister Petter LP612G1 | 58.8 | Datasheet |
| 4U-L325 | 358 | 325 | Lister Petter LP612G2 | 66.9 | Datasheet |
| 4U-L350 | 385 | 350 | Lister Petter LP612G3 | 72.9 | Datasheet |
| 4U-L375 | 413 | 375 | Lister Petter LP613G1 | 79 | Datasheet |