Cummins generating set · 50 Hz
4U-C300 — 300 kVA prime / 330 kVA standby Cummins diesel generator
300 kVA prime / 330 kVA standby, powered by a Cummins 6LTAA9.5-G1 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.
- 300 kVA prime
- 330 kVA standby
- Cummins 6LTAA9.5-G1
- 1-year warranty

Output ratings
| Standby (ESP) | 330 kVA / 264 kW |
|---|---|
| Prime (PRP) | 300 kVA / 240 kW |
| Voltage / frequency | 400/230 V · 3-phase · 50 Hz · 1500 rpm |
| Power factor | 0.8 |
| Other voltages | 380/220 · 415/240 · 440/254 · 480/277 V |
Engine
| Make / model | Cummins 6LTAA9.5-G1 |
|---|---|
| Cylinders | 6 in-line |
| Displacement | 9.5 L |
| Bore × stroke | 116 × 148 mm |
| Aspiration | Turbocharged, air-to-air charge cooled |
| Governing | Electronic |
| Cooling | Water cooled, radiator for 50 °C ambient |
| Coolant capacity | 55.5 L |
| Lube oil capacity | 28.1 L |
Alternator
| Make | 4U · Leroy-Somer | Stamford |
|---|---|
| Leroy-Somer frame | TAL-A46-F |
| Stamford frame | HCI444D/S4L1DD41 |
| Type | Self-excited, 4-pole, single bearing |
| Insulation / protection | Class H · IP23 |
| Voltage regulation | ± 1 % |
Fuel consumption
| 50 % prime load | 35 L/h |
|---|---|
| 75 % prime load | 52 L/h |
| 100 % prime load | 70 L/h |
| Standby rating | 78 L/h |
Dimensions & weight
| Open set (L × W × H) | 2850 × 1420 × 2130 mm |
|---|---|
| Open set weight | 2,650 kg |
| Silent canopy (L × W × H) | 5205 × 1625 × 2620 mm |
| Canopy weight | 4,000 kg |
| Base fuel tank | 625 L |
| Noise @ 7 m | 83 dB(A) ± 3 |
Control & protection
| Controller | Deep Sea DSE6120 — auto start / AMF |
|---|---|
| Main breaker | 3-pole LS MCCB |
| Shutdowns & alarms | Over/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop |
| Warranty | 12 months or 1,000 running hours, whichever first |
- Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
- Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
- Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.
Request this spec