Skip to content
4U PowerGenerationFZC

Cummins generating set · 50 Hz

4U-C135 — 135 kVA prime / 150 kVA standby Cummins diesel generator

135 kVA prime / 150 kVA standby, powered by a Cummins 6BTAA5.9-G2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 135 kVA prime
  • 150 kVA standby
  • Cummins 6BTAA5.9-G2
  • 1-year warranty
4U-C135 — 135 kVA prime / 150 kVA standby Cummins diesel generator

Output ratings

Output ratings — 4U-C135
Standby (ESP)150 kVA / 120 kW
Prime (PRP)135 kVA / 108 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-C135
Make / modelCummins 6BTAA5.9-G2
Cylinders6 in-line
Displacement5.9 L
Bore × stroke102 × 120 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity10 L
Lube oil capacity14.2 L

Alternator

Alternator — 4U-C135
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A44-H
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-C135
50 % prime load16 L/h
75 % prime load23 L/h
100 % prime load30 L/h
Standby rating34 L/h

Dimensions & weight

Dimensions & weight — 4U-C135
Open set (L × W × H)2550 × 1260 × 1900 mm
Open set weight1,750 kg
Silent canopy (L × W × H)3894 × 1355 × 2208 mm
Canopy weight2,310 kg
Base fuel tank543 L
Noise @ 7 m77 dB(A) ± 3

Control & protection

Control & protection — 4U-C135
ControllerDeep Sea DSE4520 — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-C100110100Cummins 6BT5.9-G125Datasheet
4U-C100B110100Cummins 6BTA5.9-G525Datasheet
4U-C135150135Cummins 6BTAA5.9-G230Datasheet
4U-C136150136Cummins 6BTAA5.9-G630Datasheet
4U-C150165150Cummins 6BTAA5.9-G1230Datasheet
All 44 Cummins models →