4U-C100B — 100 kVA prime / 110 kVA standby Cummins diesel generator

100 kVA prime / 110 kVA standby, powered by a Cummins 6BTA5.9-G5 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 100 kVA prime
  • 110 kVA standby
  • Cummins 6BTA5.9-G5
  • 1-year warranty
4U-C100B — 100 kVA prime / 110 kVA standby Cummins diesel generator

Output ratings

Output ratings — 4U-C100B
Standby (ESP)110 kVA / 88 kW
Prime (PRP)100 kVA / 80 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-C100B
Make / modelCummins 6BTA5.9-G5
Cylinders6 in-line
Displacement5.9 L
Bore × stroke102 × 120 mm
AspirationTurbocharged & aftercooled
GoverningElectronic
CoolingWater cooled, radiator for 54 °C ambient
Coolant capacity19.8 L
Lube oil capacity16.4 L

Alternator

Alternator — 4U-C100B
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A44D
Stamford frameUCI274D
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-C100B
50 % prime load12 L/h
75 % prime load18 L/h
100 % prime load25 L/h
Standby rating27 L/h

Dimensions & weight

Dimensions & weight — 4U-C100B
Open set (L × W × H)2195 × 900 × 1445 mm
Open set weight1,162 kg
Silent canopy (L × W × H)2977 × 1155 × 1693 mm
Canopy weight1,360 kg
Base fuel tank269 L
Noise @ 7 m73 dB(A) ± 3

Control & protection

Control & protection — 4U-C100B
ControllerDeep Sea DSE4520 — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-C809280Cummins 4BTAA3.9-G1117.6Datasheet
4U-C100110100Cummins 6BT5.9-G125Datasheet
4U-C100B110100Cummins 6BTA5.9-G525Datasheet
4U-C135150135Cummins 6BTAA5.9-G230Datasheet
4U-C136150136Cummins 6BTAA5.9-G630Datasheet
All 44 Cummins models →
CallWhatsApp