Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P500 — 500 kVA prime / 550 kVA standby Perkins diesel generator

500 kVA prime / 550 kVA standby, powered by a Perkins 2506A-E15TAG2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 500 kVA prime
  • 550 kVA standby
  • Perkins 2506A-E15TAG2
  • 1-year warranty
4U-P500 — 500 kVA prime / 550 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P500
Standby (ESP)550 kVA / 440 kW
Prime (PRP)500 kVA / 400 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P500
Make / modelPerkins 2506A-E15TAG2
Cylinders6 in-line
Displacement15.2 L
Bore × stroke137 × 171 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity58 L
Lube oil capacity62 L

Alternator

Alternator — 4U-P500
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A47-C
Stamford frameHCI544D / S5L1D-C41
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P500
50 % prime load55 L/h
75 % prime load81 L/h
100 % prime load106 L/h
Standby rating114 L/h

Dimensions & weight

Dimensions & weight — 4U-P500
Open set (L × W × H)3500 × 1695 × 2275 mm
Open set weight3,800 kg
Silent canopy (L × W × H)5170 × 1590 × 2600 mm
Canopy weight5,000 kg
Base fuel tank1,020 L
Noise @ 7 m83 dB(A) ± 3

Control & protection

Control & protection — 4U-P500
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P400450400Perkins 2206A-E13TAG393Datasheet
4U-P455500455Perkins 2506A-E15TAG199Datasheet
4U-P500550500Perkins 2506A-E15TAG2106Datasheet
4U-P600660600Perkins 2806A-E18TAG1A129Datasheet
4U-P650700650Perkins 2806A-E18TAG2132Datasheet
All 42 Perkins models →
CallWhatsApp