Perkins generating set · 50 Hz
4U-P275 — 275 kVA prime / 300 kVA standby Perkins diesel generator
275 kVA prime / 300 kVA standby, powered by a Perkins 1506A-E88TAG4 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.
- 275 kVA prime
- 300 kVA standby
- Perkins 1506A-E88TAG4
- 1-year warranty

Output ratings
| Standby (ESP) | 300 kVA / 240 kW |
|---|---|
| Prime (PRP) | 275 kVA / 220 kW |
| Voltage / frequency | 400/230 V · 3-phase · 50 Hz · 1500 rpm |
| Power factor | 0.8 |
| Other voltages | 380/220 · 415/240 · 440/254 · 480/277 V |
Engine
| Make / model | Perkins 1506A-E88TAG4 |
|---|---|
| Cylinders | 6 in-line |
| Displacement | 8.8 L |
| Bore × stroke | 112 × 149 mm |
| Aspiration | Turbocharged, air-to-air charge cooled |
| Governing | Electronic |
| Cooling | Water cooled, radiator for 50 °C ambient |
| Coolant capacity | 33.2 L |
| Lube oil capacity | 39 L |
Alternator
| Make | 4U · Leroy-Somer | Stamford |
|---|---|
| Leroy-Somer frame | TAL-A46-E |
| Stamford frame | S4L1D-D41 |
| Type | Self-excited, 4-pole, single bearing |
| Insulation / protection | Class H · IP23 |
| Voltage regulation | ± 1 % |
Fuel consumption
| 50 % prime load | 33 L/h |
|---|---|
| 75 % prime load | 48 L/h |
| 100 % prime load | 65 L/h |
| Standby rating | 73 L/h |
Dimensions & weight
| Open set (L × W × H) | 3080 × 1200 × 1830 mm |
|---|---|
| Open set weight | 2,780 kg |
| Silent canopy (L × W × H) | 4414 × 1614 × 2235 mm |
| Canopy weight | 3,440 kg |
| Base fuel tank | 760 L |
| Noise @ 7 m | 80 dB(A) ± 3 |
Control & protection
| Controller | Deep Sea DSE6110 MKII — auto start / AMF |
|---|---|
| Main breaker | 3-pole LS MCCB |
| Shutdowns & alarms | Over/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop |
| Warranty | 12 months or 1,000 running hours, whichever first |
- Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
- Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
- Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.
Request this spec
Typical reply: within 1 working hour on WhatsApp
Nearby models
| Model | Standby kVA | Prime kVA | Engine | Fuel 100% (L/h) | Datasheet |
|---|---|---|---|---|---|
| 4U-P250 | 275 | 250 | Perkins 1206A-E70TTAG3 | 56.9 | Datasheet |
| 4U-P250B | 275 | 250 | Perkins 1506A-E88TAG3 | 56.9 | Datasheet |
| 4U-P275 | 300 | 275 | Perkins 1506A-E88TAG4 | 65 | Datasheet |
| 4U-P300 | 330 | 300 | Perkins 1506A-E88TAG5 | 65 | Datasheet |
| 4U-P300B | 330 | 300 | Perkins 1706A-E93TAG1 | 65 | Datasheet |