Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P230 — 230 kVA prime / 250 kVA standby Perkins diesel generator

230 kVA prime / 250 kVA standby, powered by a Perkins 1506A-E88TAG2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 230 kVA prime
  • 250 kVA standby
  • Perkins 1506A-E88TAG2
  • 1-year warranty
4U-P230 — 230 kVA prime / 250 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P230
Standby (ESP)250 kVA / 200 kW
Prime (PRP)230 kVA / 184 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P230
Make / modelPerkins 1506A-E88TAG2
Cylinders6 in-line
Displacement8.8 L
Bore × stroke112 × 149 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity25 L
Lube oil capacity13 L

Alternator

Alternator — 4U-P230
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A46-C
Stamford frameUCD274K
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P230
50 % prime load27.8 L/h
75 % prime load40.4 L/h
100 % prime load54.5 L/h
Standby rating61.5 L/h

Dimensions & weight

Dimensions & weight — 4U-P230
Open set (L × W × H)3015 × 1000 × 1980 mm
Open set weight2,000 kg
Silent canopy (L × W × H)4414 × 1600 × 2250 mm
Canopy weight3,290 kg
Base fuel tank760 L
Noise @ 7 m73 dB(A) ± 3

Control & protection

Control & protection — 4U-P230
ControllerDeep Sea DSE6110 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P200B225200Perkins 1206A-E70TAG154.5Datasheet
4U-P225250225Perkins 1206A-E70TTAG248.6Datasheet
4U-P230250230Perkins 1506A-E88TAG254.5Datasheet
4U-P250275250Perkins 1206A-E70TTAG356.9Datasheet
4U-P250B275250Perkins 1506A-E88TAG356.9Datasheet
All 42 Perkins models →