Skip to content
4U PowerGenerationFZC

Perkins generating set · 50 Hz

4U-P100 — 100 kVA prime / 110 kVA standby Perkins diesel generator

100 kVA prime / 110 kVA standby, powered by a Perkins 1104C-44TAG2 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 100 kVA prime
  • 110 kVA standby
  • Perkins 1104C-44TAG2
  • 1-year warranty
4U-P100 — 100 kVA prime / 110 kVA standby Perkins diesel generator

Output ratings

Output ratings — 4U-P100
Standby (ESP)110 kVA / 88 kW
Prime (PRP)100 kVA / 80 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-P100
Make / modelPerkins 1104C-44TAG2
Cylinders4 in-line
Displacement4.4 L
Bore × stroke105 × 127 mm
AspirationTurbocharged, air-to-air charge cooled
GoverningElectronic
CoolingWater cooled, radiator for 50 °C ambient
Coolant capacity12.6 L
Lube oil capacity8 L

Alternator

Alternator — 4U-P100
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameTAL-A44-D
Stamford frameUCI274D
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-P100
50 % prime load11.3 L/h
75 % prime load17.1 L/h
100 % prime load22.6 L/h
Standby rating24.9 L/h

Dimensions & weight

Dimensions & weight — 4U-P100
Open set (L × W × H)2195 × 900 × 1445 mm
Open set weight1,295 kg
Silent canopy (L × W × H)2977 × 1155 × 1695 mm
Canopy weight1,683 kg
Base fuel tank269 L
Noise @ 7 m78 dB(A) ± 3

Control & protection

Control & protection — 4U-P100
ControllerDeep Sea DSE4520 MKII — auto start / AMF
Main breaker3-pole LS MCCB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-P606660Perkins 1103A-33TG214Datasheet
4U-P808880Perkins 1104A-44TG214Datasheet
4U-P100110100Perkins 1104C-44TAG222.6Datasheet
4U-P135150135Perkins 1106A-70TG130.2Datasheet
4U-P150165150Perkins 1106A-70TAG233Datasheet
All 42 Perkins models →
CallWhatsApp