Lister Petter generating set · 50 Hz
4U-L125 — 125 kVA prime / 138 kVA standby Lister Petter diesel generator
125 kVA prime / 138 kVA standby, powered by a Lister Petter LP443G6 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.
- 125 kVA prime
- 138 kVA standby
- Lister Petter LP443G6
- 1-year warranty

Output ratings
| Standby (ESP) | 138 kVA / 110 kW |
|---|---|
| Prime (PRP) | 125 kVA / 100 kW |
| Voltage / frequency | 400/230 V · 3-phase · 50 Hz · 1500 rpm |
| Power factor | 0.8 |
| Other voltages | 380/220 · 415/240 · 440/254 · 480/277 V |
Engine
| Make / model | Lister Petter LP443G6 |
|---|---|
| Cylinders | 4 in-line |
| Displacement | 4.3 L |
| Bore × stroke | 105 × 124 mm |
| Aspiration | Turbocharged, air-to-air charge cooled |
| Governing | Electronic |
| Cooling | Water cooled, radiator for 52 °C ambient |
| Coolant capacity | 32 L |
| Lube oil capacity | 13 L |
Alternator
| Make | 4U · Leroy-Somer | Stamford |
|---|---|
| Leroy-Somer frame | TAL-A44-H |
| Type | Self-excited, 4-pole, single bearing |
| Insulation / protection | Class H · IP23 |
| Voltage regulation | ± 1 % |
Fuel consumption
| 50 % prime load | 14.4 L/h |
|---|---|
| 75 % prime load | 21.3 L/h |
| 100 % prime load | 28.3 L/h |
| Standby rating | 31.5 L/h |
Dimensions & weight
| Open set (L × W × H) | 2500 × 1050 × 1510 mm |
|---|---|
| Silent canopy (L × W × H) | 2980 × 1100 × 1830 mm |
| Base fuel tank | 300 L |
Control & protection
| Controller | Deep Sea DSE4520 MKII — auto start / AMF |
|---|---|
| Main breaker | 3-pole LS Electric |
| Shutdowns & alarms | Over/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop |
| Warranty | 12 months or 1,000 running hours, whichever first |
- Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
- Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
- Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.
Request this spec
Typical reply: within 1 working hour on WhatsApp
Nearby models
| Model | Standby kVA | Prime kVA | Engine | Fuel 100% (L/h) | Datasheet |
|---|---|---|---|---|---|
| 4U-L100 | 110 | 100 | Lister Petter LP443G4 | 23 | Datasheet |
| 4U-L113 | 125 | 113 | Lister Petter LP443G5 | — | Datasheet |
| 4U-L125 | 138 | 125 | Lister Petter LP443G6 | 28.3 | Datasheet |
| 4U-L125B | 138 | 125 | Lister Petter TR661G2 | 30.7 | Datasheet |
| 4U-L138 | 150 | 138 | Lister Petter LP665G1 | 30.5 | Datasheet |