Skip to content
4U PowerGenerationFZC

Cummins generating set · 50 Hz

4U-C1416 — 1,416 kVA prime / 1,650 kVA standby Cummins diesel generator

1416 kVA prime / 1650 kVA standby, powered by a Cummins KTA50-G8 engine with a Leroy-Somer or Stamford alternator and Deep Sea controller. Supplied open or in a silent canopy, with delivery, installation and commissioning across the UAE.

  • 1416 kVA prime
  • 1650 kVA standby
  • Cummins KTA50-G8
  • 1-year warranty
4U-C1416 — 1,416 kVA prime / 1,650 kVA standby Cummins diesel generator

Output ratings

Output ratings — 4U-C1416
Standby (ESP)1,650 kVA / 1,320 kW
Prime (PRP)1,416 kVA / 1,132.8 kW
Voltage / frequency400/230 V · 3-phase · 50 Hz · 1500 rpm
Power factor0.8
Other voltages380/220 · 415/240 · 440/254 · 480/277 V

Engine

Engine — 4U-C1416
Make / modelCummins KTA50-G8
Cylinders16 in 60° V
Displacement50.3 L
Bore × stroke159 × 159 mm
AspirationTurbocharged & aftercooled
GoverningElectronic
CoolingWater cooled, radiator for 48 °C ambient
Coolant capacity496 L
Lube oil capacity178 L

Alternator

Alternator — 4U-C1416
Make4U · Leroy-Somer | Stamford
Leroy-Somer frameLSA50.2 L8
Stamford frameS7L1D-D41
TypeSelf-excited, 4-pole, single bearing
Insulation / protectionClass H · IP23
Voltage regulation± 1 %

Fuel consumption

Fuel consumption — 4U-C1416
50 % prime load155 L/h
75 % prime load222 L/h
100 % prime load289 L/h
Standby rating345 L/h

Dimensions & weight

Dimensions & weight — 4U-C1416
Open set (L × W × H)5830 × 2280 × 3065 mm
Open set weight12,700 kg
Silent canopy (L × W × H)9209 × 2292 × 3615 mm
Canopy weight18,400 kg
Base fuel tankExternal day tank (sized to site)
Noise @ 7 m88 dB(A) ± 3

Control & protection

Control & protection — 4U-C1416
ControllerDeep Sea DSE6120 — auto start / AMF
Main breakerSchneider ACB
Shutdowns & alarmsOver/under speed & voltage, over-current, low oil pressure, high engine temperature, battery, start/stop failure, emergency stop
Warranty12 months or 1,000 running hours, whichever first
  • Prime (PRP): unlimited hours at an average 80 % load over each 24 h, with 10 % overload for 1 h in every 12 h.
  • Standby (ESP): up to 500 h a year at an average 80 % load during mains failure; no overload.
  • Options: silent canopy or container, external tank (500–5,000 L), ATS panel, synchronising, 55 °C radiator, engine heaters.

Request this spec

Typical reply: within 1 working hour on WhatsApp

By sending this form you agree to our privacy policy.

Nearby models

4U generator models
ModelStandby kVAPrime kVAEngineFuel 100% (L/h)Datasheet
4U-C1000B1,1001,000Cummins QST30-G4202Datasheet
4U-C12501,3751,250Cummins KTA50-G3261Datasheet
4U-C14161,6501,416Cummins KTA50-G8289Datasheet
4U-C15001,6501,500Cummins KTA50-GS8309Datasheet
4U-C16081,9131,608Cummins KTA50-G9330Datasheet
All 44 Cummins models →
CallWhatsApp